The flow checker mounts directly to the discharge
of PZ and PZi metering pumps.
The flow checker is an oval gear flow meter
which measures the pump output and transmits
one pulse for each 1 ml of flow.
Flow checker output can be connected to
Model PZi8 Pumps for instantaneous indication
of pump output displayed on the pump LCD.
Connect the flow checker output to your
controller or PLC (external power supply
required if not used with PZi8 type pump).
Feed Verification
Feed Verification
FLOW CHECKER SELECTION CHART
MODEL NO. MATERIAL USE w/ PUMP MODEL†
FC-1P-P-N1 Ryton* PZ or PZi-31
FC-1N-P-N1 Noryl** PZ or PZi-31
FC-1P-P-N2 Ryton* PZ or PZi-61 or -12
FC-1N-P-N2 Noryl** PZ or PZi-61 or -12
Not available for larger models.
DIMENSIONS
inches (mm)
SPECIFICATIONS
Pulse constant 1mL/pulse
Accuracy ±3% (Depends on nature of chemical,
flow rate, temperature and back pressure.)
Normal operating pressure 140 psi (10 Kg/cm
2
)
Momentary maximum 200 psi (14 Kg/cm
2
)
operating pressure
Temperature 32–104°F (040°C) (Liquid should not freeze.)
Liquid viscosity 1 to 50 cps
Output Open collector (Collector capacity: 30V, 30mA)
Power requirement 4.5 to 25VDC (20mA Max.)*
Green LED lights for each pulse output. Red LED on when the power is ON.
NOTES: 1. Use flow checker only for clear liquids.
2. Pressure loss is 0.5 Kg/cm
2
(at maximum flow rate using water).
*
+ 5V Power Supply provided on board PZi8 Models.
LIQUID-END MATERIALS
PART MODEL MODEL
NAME FC -1P- FC -1N-
Body Ryton* Noryl**
Ball Check Ceramic Ceramic
Ball Guide/Joint PVC PVC
Valve Seat/O-Ring EPDM Fluororubber
* Ryton: PPS Polyphenylene-sulfide (for general chemicals)
** Noryl: PPO Polyphenylene-oxide (for sodium hypochlorite)
3-3/8'' (85)
2-3/8'' (60)
2-5/8'' (66)
LED: RED
2'' (50)
2
LED: GREEN
2'' (48)
1
-1/2'' (39)
6'' (149)
The Model FC-1 Flow Checker output provides
vital information for water treatment programs
requiring feed verification to manage chemistry
and monitor drum inventory.
Model FC-1
FLOW CHECKER
MATERIAL SELECTION CHART
PUMPING LIQUID CONCENTRATION RECOMMENDED
(in alphabetical order)
TYPE
Acetic acid 50% VFC/FFC
Acetic acid concentrated 24°C FTC
Aluminum sulfate VEC
Amine* SS
Aqueous ammonia VEC
Calcium/Sodium
hypochlorite
12% CL/AR
Caustic soda VEC
Ferric/Ferrous chloride VFC
Ferric/Ferrous sulfate VFC
Hydrochloric acid 10% to conc. VFC
Hydrogen peroxide 30% VFC
Nitric acid 10% VFC
Nitric acid 30% to conc. FTC
Phosphoric acid 10% to conc. FTC
Poly-aluminum
chloride (PAC)
VEC
Potassium
permanganate
VEC
Sulfuric acid to 40% VFC/FFC
Sulfuric acid concentrated FTC
*Boiler compounds with small amounts of Amine FEC
CAUTION ALL MODELS
Ambient temperature: 32 to 104°F (0 to 40°C)
Pumped liquids:
Temperature: 32 to 104°F (0 to 40°C),
Viscosity: 100 CPS max. except as noted
This pump is designed for outdoor use. Avoid
installing pump in a location where service life
could be shortened (i.e., where it is exposed to
direct sunlight or driving rain).
This pump cannot pump liquids containing a slurry.
A relief valve should be installed on the discharge
side, if the pump does not have a built-in relief
valve and the discharge piping has a shutoff valve.
I
NCLUDED WITH
EACH PUMP:
F
oot Valve Strainer*
Back Pressure/Check Valve
Injector with Quill*
Suction, Discharge and
Air Release Tubing*
Power Cord with 3-Prong Plug
Signal Cable with Multi-Pin Connectors
(one with PZi4 & two with PZi8 & PZiG models)
*except some PZiG models (see page 4)
Foot Valve
Strainer
Back Pressure
Injector
(shown with
PZi8 type
pump)
TRIM 5/8" OFF OF THIS SIDE TO CLEAR HOLE DRILL
5